5. Configuration
5.6. Configuring Advanced Alarming
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 227
July 2010 Honeywell
the Configuration dialog box
.
Configuring/creating a condition
To
configure a condition, perform the following steps.
Step Action
1
From the Configure Advanced Alarming dialog box, click Condition
Listing tab.
2
Click New.
The Condition Configuration dialog box appears.