EasyManua.ls Logo

Honeywell Series A - Out_Hi_Lim; Out_Lo_Lim; Out_Scale

Honeywell Series A
560 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 463
July 2010 Honeywell
OUT_HI_LIM
Classification
Simple Variable
Description
Defines the maximum output value limit in all modes,
unless the CONTROL_OPTS selection No Out limits in
Manual is chosen.
FF Data Type
Float
Range
OUT_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
Initial value is 100.
OUT_LO_LIM
Classification
Simple Variable
Description
Defines the minimum output value limit in all modes, unless
the CONTROL_OPTS selection No Out limits in Manual is
chosen.
FF Data Type
Float
Range
OUT_SCALE +/- 10 percent
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
Initial value is 0.
OUT_SCALE

Table of Contents