8. Maintenance, Checkout, and Calibration
8.4. Correcting Some Common UTR errors
328 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
8.4 Correcting Some Common UTR errors
The following table identifies some common errors that may occur during an UTR
operation and offers some suggested corrective action.
If You Encounter This Problem . . . Then, Take This Corrective Action . . .
Device is loaded to Monitoring side of Control
Builder
Delete the device from Monitoring side. Use
the Force Delete function, if necessary. This
may also require the device's blocks to be
deleted from the Control Module on the
Monitoring side.
Device is locked Locate the source of the lock.
Block loss with control connections
Select another fieldbus device type for
replacement, which can support all blocks
that have connections.
Change the control strategy to eliminate
the control connection(s) to the block that
does not match.
Insufficient VCR's
Insufficient FB Start Entries
Insufficient Link Objects.
Select another fieldbus device type that
has a sufficient number of resources.
Alternatively (although not recommended
since the intended results may be difficult
to obtain), the user may also modify the
control strategy to reduce the number of
resources required. This may work,
although the user may have to go through
several rounds of trial and error before
eliminating the error.
8.5 Upgrading Firmware in Uncommissioned Device
Use the following procedure to upgrade the firmware in an uncommissioned device
through Control Builder. This procedure assumes that you have the vendor supplied
upgrade file for the device. It also assumes that you are monitoring the FIM/LINK
through the Monitoring tab in Control Builder.
CAUTION
Do not upgrade firmware in Honeywell model ST3000 or model STT35F, or
Flowserve Logic 1400 devices on a running fieldbus link. Be sure to take all