11. Appendix B
11.1. Standard Function Block Parameters
436 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Classification
Simple Variable
Description
Identifies state of discrete input that will generate an alarm.
FF Data Type
Unsigned 8
Range
PV state
Usage
C/Contained
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
DISC_PRI
Classification
Simple Variable
Description
Identifies the priority of the discrete alarm.
FF Data Type
Unsigned 8
Range
0 to 63
Usage
C/Alert Priority
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
DV_HI_ALM
Classification
Record
Description
Identifies the status and time stamp associated with the
high deviation alarm.
FF Data Type
DS-71