11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 477
July 2010 Honeywell
SEL_TYPE
Classification
Simple Variable
Description
Defines the type of selector action as High, Medium, or
Low.
FF Data Type
Unsigned 8
Range
1: High
2: Low
3: Medium
Usage
C/Contained
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
SET_FSTATE
Classification
Simple Variable
Description
Allows the fault state condition to be manually initiated by
selecting Set.
FF Data Type
Unsigned 8
Range
1: Off
2: Set
Usage
C/Contained
Length
1
Valid Views
Storage
Dynamic
Remarks
The operator can control PROGRAM or LOCAL access to
this value.