11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 435
July 2010 Honeywell
Range
Usage
C/Contained
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
Read Only
DISC_ALM
Classification
Record
Description
Identifies the status and time stamp associated with the
discrete alarm.
FF Data Type
DS-72
Range
Usage
C/Alarm
Length
13
Valid Views
Storage
Dynamic
Remarks
Read Only
The data type consists of data that describes discrete
alarms. It uses the following five elements.
1 Unacknowledged
2 Alarm State
3 Time Stamp
4 Subcode
5 Value
DISC_LIM