11. Appendix B 
11.1. Standard Function Block Parameters 
462  Experion PKS Series A Fieldbus Interface Module User's Guide   R400 
 Honeywell July 2010 
Usage 
O/Primary Output 
Length 
5 
Valid Views 
VIEW_1, VIEW_3 
Storage 
Non-Volatile 
Remarks 
Normally, the operator has permission to write this value, 
but PROGRAM or LOCAL remove that permission and 
grant it to a supervisory computer or a local control panel. 
The Data type consists of the value and status of floating 
point parameters that are Inputs or Outputs. It uses the 
following two elements.  
    1 Status 
    2 Value 
 
 
OUT_D 
 
Classification 
Record 
Description 
Represents the primary discrete value calculated as a 
result of executing the function.  
FF Data Type 
DS-66 
Range 
OUT_STATE 
Usage 
O/Primary Output 
Length 
2 
Valid Views 
VIEW_1, VIEW_3 
Storage 
Non-Volatile 
Remarks 
Normally, the operator has permission to write this value, 
but PROGRAM or LOCAL remove that permission and 
grant it to a supervisory computer or a local control panel. 
The data type consists of the value and status of discrete 
value parameters. It uses the following two elements.  
    1 Status 
    2 Value