EasyManua.ls Logo

Honeywell Series A - Non-Redundant Fieldbus integrated architecture for CIOM-A FIM

Honeywell Series A
560 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Fieldbus Integration With Experion System
3.1. Overview
34 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Non-Redundant Fieldbus integrated architecture for CIOM-A FIM
The following figure shows a typical non-redundant fieldbus architecture using a CIOM-
A Fieldbus Interface Module (FIM) in a non-redundant C200 Controller and a remote I/O
chassis configuration. The FIM serves as the communication gateway between the
Supervisory ControlNet and/or I/O ControlNet network and the Foundation Fieldbus H1
communications medium. It includes a Remote Termination Panel (RTP) for connecting
and powering up to two fieldbus H1 links.
Ethernet (TCP/IP)
Remote
I/O Chassis
Remote
I/O Chassis
Redundant
Servers
PT
PT
Supervisory ControlNet/Ethernet
I/O ControlNet
I/O ControlNet
Redundant
Controllers
Non-Redundant
Controller
Station
PT
PT
PT
PT
PT
PT
24Vdc
(Optional)
24Vdc
(Optional)
Remote
Termination
Panel
Remote
Terminat io n
Panel
FIM
FIM
H1 Link 1
H1 Link 1
H1 Link 2
H1 Link 2
F Fieldbus
OUNDATION
Compliant Devices
F Fieldbus
OUNDATION
Compliant Devices
24Vdc
Conditioned
24Vdc
Conditioned
24Vdc
Conditioned
24Vdc
Conditioned
Notes
:
FIM = Fieldbus Interface Module
Only ControlNet is available as redundant media.
Figure 1 Sample system architecture for non-redundant Fieldbus
integration for CIOM-A FIM.