11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 475
July 2010 Honeywell
6: Failure
Usage
C/Resource State
Length
1
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
Read Only
SEL_1
Classification
Record
Description
Represents first input value to the selector.
FF Data Type
DS-65
Range
Usage
I/Cascade Input
Length
5
Valid Views
VIEW_1, VIEW_3
Storage
Non-Volatile
Remarks
Read Only
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
SEL_2
Classification
Record
Description
Represents second input value to the selector.
FF Data Type
DS-65