11. Appendix B
11.1. Standard Function Block Parameters
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 423
July 2010 Honeywell
BKCAL_OUT
Classification
Record
Description
The value and status required by an upper block's
BKCAL_IN so the upper block may prevent reset windup
and provide bumpless transfer to closed loop control.
FF Data Type
DS-65
Range
Usage
O/Back Calculation Output
Length
5
Valid Views
VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
BKCAL_OUT_D
Classification
Record
Description
The output value and status provided to an upstream
discrete block that is used to provide bumpless transfer for
closed loop control.
FF Data Type
DS-66
Range
Usage
O/Back Calculation Output
Length
2
Valid Views
VIEW_3
Storage
Dynamic