11. Appendix B
11.1. Standard Function Block Parameters
474 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
ROUT_OUT
Classification
Record
Description
Represents block output and status. It serves as input to a
host for back calculation in ROut mode that allows action to
be taken under limited conditions or mode change
FF Data Type
DS-65
Range
Usage
C/Remote-Output Out
Length
5
Valid Views
VIEW_3
Storage
Dynamic
Remarks
Read Only
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
RS_STATE
Classification
Simple Variable
Description
Defines the state of the function block application state
machine.
FF Data Type
Unsigned 8
Range
1: Start/Restart
2: Initialization
3: On-Line Linking
4: On-Line
5: Standby