11. Appendix B 
11.1. Standard Function Block Parameters 
R400  Experion PKS Series A Fieldbus Interface Module User's Guide  447 
July 2010  Honeywell 
Classification 
Record 
Description 
Defines options for controlling access of host computer or 
local control panels to the block's operating, tuning, and 
alarm parameters.  
FF Data Type 
DS-70 
Range 
 
Usage 
C/Access Permission 
Length 
2 
Valid Views 
VIEW_2 
Storage 
Non-Volatile 
Remarks 
The data type consists of access control flags for access to 
block parameters. It uses the following two elements.  
    1 Grant 
    2 Deny 
 
HARD_TYPES 
 
Classification 
Simple Variable 
Description 
Identifies types of hardware that are available as channel 
numbers on this resource.  
FF Data Type 
Bit String 
Range 
Set by manufacturer 
Usage 
C/Contained 
Length 
2 
Valid Views 
VIEW_4 
Storage 
Static 
Remarks 
Read Only 
 
HI_ALM