5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 175
July 2010 Honeywell
Step Action Result
4
Key in >CM101<. Click in Item Name
field.
Moves cursor to the Item Name field.
5
Key in the name of the Entity that this
object will be associated with in the
Enterprise Model Builder hierarchy.
Press <Tab>.
Moves cursor to the Description field.
5
Key in >Surge Tank Control Loop<.
Press <Tab>.
Moves cursor to the Eng. Units field.
6
Key in >Percent<. Press <Tab>.
Moves cursor to Keyword field
7
Key in >Recycle<. Press <Tab>.
Moves cursor to Enable Alarming Option
check box.
8
Accept the default alarm enabled
selection - box checked. Press <Tab>.
Moves cursor to Execution Order in CEE
field and highlights it.
ATTENTION
The Execution Order in CEE parameter only applies to contained Experion function
blocks in CM's that are assigned to a CEE. It has no affect on contained fieldbus
blocks and it is disabled, if the CM is assigned to a Link.