5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 185
July 2010 Honeywell
Step Action Result
7
Click checkbox to grant Program
Operations for this example. Click the OK
button
Closes Block Parameter form and stores
the configuration entries.
ATTENTION
For this example, we will skip the other tabs on the Block Parameters form, since a
DATAACQ block will be used for alarm purposes. Please feel free to practice entering
data in the other tabs, using the online Help for support.
8
This completes the AI block configuration
for the sample loop. Go to the next
procedure Configuring DATAACQ block
for sample loop.
Configuring DATAACQ block for sample loop
Step Action Result
1
In CM101 chart, double-click DATAACQ
block.
Opens DATAACQ Block Parameters
form with Name field highlighted.