5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 191
July 2010 Honeywell
Step Action Result
21
Scroll the Parameters list box to
find PV. Click it.
Click Left/Right in Pin/Position box.
Click the Add button.
Adds PV as visible block output pin on
the right-hand side of the block.
22
Click the OK button.
Closes the Block Parameters form and
stores the configuration entries.
ATTENTION
For this example, we will accept the default values for the other parameters on the
Block Pins tab as well as the remaining tabs. These values are okay for the sample
loop. Please feel free to practice entering data in the other tabs, using the online Help
for support.
23
This completes the DATAACQ block
configuration. Go to the next procedure
Configuring PID block for sample loop.
Configuring PID block for sample loop
Step Action Result
1
In CM101 chart, double-click PIDA block.
Opens PID Block Parameters form with
Name field highlighted.