5. Configuration
5.5. Loading Components Online
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 213
July 2010 Honeywell
Step Action Result
4
Click the Yes button.
Initiates Link startup. CIOM-A FIM icon
turns green and LINK icon turns yellow.
5
Wait for LINK 1 to startup and icon to turn
green.
LINK 1 is now active and detects any
uncommissioned devices connected
to it.
TIP
If a connected fieldbus device is not being detected by the link, try increasing the Slot
Time value through the LINK Block Parameters configuration form. With Link icon
selected, click Edit>Configure Module Properties, click the Network Management (LM)
tab, select the Slot Time field (default value is 8), key in 10, press <Enter>, click OK,
wait for the value to change, and click OK to close the form.
6
On the Project tab,click Field Devices-
>Device Match.
Calls up Link Parameters form with
Device Matching Dialog tab selected. The
following illustration is for example
purposes only.