5. Configuration
5.5. Loading Components Online
216 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
TIP
If the Uncommissioned Devices were previously configured through a Hand-Held
Communicator or third-party configurator to contain correct tag and address data, use
the Match from Uncommissioned Device to Project Device button to preserve the
Uncommissioned Device data and change the Project Device data to match it.
If Uncommissioned device contains factory default data, use the Match from Project
Device to Uncommissioned Device button to preserve the Project Device data and
change the Uncommissioned Device data to match it.
8
Click Match from Project Device to
Uncommissioned Device button for the
sample matches shown above.
Warning prompt asks if you want to
continue this operation.
(Note that the Warning prompt only
appears, if the tag and/or address of the
matching device need to be changed.
Otherwise, see the result in Step 10.)