5. Configuration
5.5. Loading Components Online
222 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
4
To change the Post Load State for
selected components, click the
appropriate Post Load State row.
Opens the dropdown menu to select
another state, as applicable.
5
Click the checkboxes to automatically
inactivate the fieldbus devices for the
load and to automatically return fieldbus
devices to post load state after the load.
Initiates automatic toggle state function
during and after the load operation.
6
Click the OK button.
Initiates "Load" and opens Load Dialog
box to show load progress. This
illustration is for example purposes only.