5. Configuration
5.6. Configuring Advanced Alarming
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 231
July 2010 Honeywell
what was set is retained on the device instance.
To enable/disable a condition, perform the following steps.
Step Action
1
From the Configure Advanced Alarming dialog box, click Condition
Listing tab.
2
Select the condition that you want to disable and clear the check box under
the Enable column.
Or
Select the condition that you want to enable and select the check box under
the Enable column.
The selected condition is disabled and the changed setting is saved in the
database.
ATTENTION
The conditions can be enabled/disabled in the Device