8. Maintenance, Checkout, and Calibration
8.1. Adding, Removing and Replacing Components
294 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
4
Connect the replacement fieldbus device
to the Link.
Wait for the replacement device to
appear as an Uncommissioned Device
(UCD) listed in the top half of the Device
Replacement dialog.
5
Click the checkbox to the left of the Tag
column for the Replacement Device.
The "Replace the Failed Device with the
Uncommissioned Replacement Device"
button becomes active.
6
Click the "Replace the Failed Device with
Uncommissioned Replacement Device"
button.
Warning prompt asks if you want to
continue.