EasyManua.ls Logo

Honeywell Series A - Page 311

Honeywell Series A
560 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8. Maintenance, Checkout, and Calibration
8.1. Adding, Removing and Replacing Components
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 311
July 2010 Honeywell
Step Action Result
29
Repeat Steps 27 and 28 for other blocks,
if required.
30
Click
close button.
Opens Save Prompt.
31
Click the Yes button. Closes chart and saves CM changes.
32
Connect the replacement fieldbus device
to the Link.
Device (ST102) appears as an
uncommissioned device (UCD) icon
in the LINK folder in the
Monitoring tab.
33
Double-click the UCD icon.
Calls up the LINK Block Parameters
Uncommissioned Devices form.

Table of Contents

Related product manuals