8. Maintenance, Checkout, and Calibration
8.6. Changing or Clearing Tag and/or Address of Uncommissioned Device
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 333
July 2010 Honeywell
Step Action Result
2
To change the tag name, key in
desired Tag (PD_TAG) name.
Usually use the tag name that
matches the one used for the Project
device. Use ST102 for this example.
Press <Enter> or click the OK
button.
To clear the tag name, just highlight
it and press <Delete>. Click the OK
button.
Warning prompt asks for confirmation of
change.
3
Click the Continue button.
Initiates change and opens progress
tracking dialog box to show status of the
change.
4
Wait for change to complete. Press
<Tab>.
Moves cursor to the Address field.