8. Maintenance, Checkout, and Calibration
8.7. Using Fieldbus Device Simulate Function
342 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
16
Check that the AI.FF OUT.VALUE is 25. Confirm that simulate value is active.
17
Close pidloop control chart. Double-click
the AI.FF block icon.
Calls up the Block Parameters form.
18
On Maintenance tab, press <Tab> four
times.
Moves cursor to Simulate En/Disable
field.