8. Maintenance, Checkout, and Calibration
8.8. Preparing Fieldbus Device for a Move or Software Migration
344 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
ATTENTION
If you do not prepare a device as outlined in the following procedure, you
may have problems loading a device after it is moved to another LINK or after
the system software has been migrated to a new release.
Step Action Result
1
In the Monitoring mode, click
symbol
for FIM, LINK, and Device icons.
Displays the FIM menu tree.
2
Right-click the function block icon. Calls up the popup menu.