8. Maintenance, Checkout, and Calibration
8.8. Preparing Fieldbus Device for a Move or Software Migration
346 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
6
On the Process tab, check that the Actual
Mode has changed to OOS.
Confirms that the block is in Out-Of-
Service (OOS) mode.
7
Click the OK button. Closes Block Parameters form.