16. Appendix G
16.1. Loading CIOM-A FIM firmware
528 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
5
In the Look in field, click the
button to navigate to this directory
location c:\Program
Files\Honeywell\Experion\Enginee
ring Tools\system\firmware\FIM, if
required.
Open appropriate release version
folder and click fimboot.nvs file so it
appears in the File name field. Click
the Open button.
Opens Please Confirm Changes
message box. This illustration is for
example purposes only.
6
Click the Yes button to acknowledge that
you want to proceed with the update.
(Note that RDY should appear in the FIM
display)
Initiates firmware load. LOAD
appears in the CIOM-A FIM display.
Progress of the load is tracked in
the status bar.
7
Wait for the load to complete and the
CIOM-A FIM to reboot to its RDY state.
NetworkTools message box appears.
8
Click the OK button to acknowledge that
the update completed with no errors.
Wait for the Ntools to complete its next
scan.
9
Check that the updated boot version (BV)
now appears on the CIOM-A FIM graphic
in green.