16. Appendix G
16.1. Loading CIOM-A FIM firmware
530 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
2
Click the Yes button to acknowledge that
system is still Offline. .
Opens the Open dialog box. This
illustration is for example purposes only.
3
In the Look in field, click the
button to navigate to this directory
location c:\Program
Files\Honeywell\Experion\Enginee
ring Tools\system\firmware\FIM, if
required.
Click fimrex.nvs file so it appears
in the File name field. Click the Open
button.
Opens the Please Confirm Changes
dialog box.
4
Click the Yes button to acknowledge that
you want to proceed with the update.
Initiates the firmware load. LOAD
appears in the CIOM-A FIM display.
Progress of the load is tracked in
the status bar.
5
Wait for load to complete and the CIOM-
A FIM to reboot to its normal run state.
NetworkTools message box appears.
6
Click the OK button to acknowledge that
the update completed with no errors.
Wait for Ntools to complete its next scan.