17. Appendix H 
17.1. Important Functional Considerations 
R400  Experion PKS Series A Fieldbus Interface Module User's Guide  535 
July 2010  Honeywell 
Function Indication  Consideration 
Preserve factory 
calibration in fieldbus 
device.  
Fieldbus device is 
supplied as Factory 
Calibrated.  
Calibration parameters should have a 
load destination of NOLOAD. Always 
initiate device match as 
Uncommissioned Device to Project 
Device. Use "partial load" when 
loading fieldbus blocks. After device 
load, do an Upload followed by an 
Update to Project to get information 
into the Monitor database.  
Using Restart with 
Defaults to restart a 
fieldbus device 
through the 
RESTART parameter 
on the Other tab of its 
Resource block 
configuration form. 
Configuration error 
notification for an 
associated block, such as 
an Analog Input block. 
Reload the device block from Project 
tab with associated blocks set for Full 
instead of Partial Load to restore 
Experion default values. For example, 
the ALERT_KEY parameter value is 
set to 2 or 1.  
A Restart with Defaults function 
restarts the device with factory default 
values instead of Experion ones.  
Unassigning Fieldbus 
block with RCAS_IN 
or ROUT_IN 
connection from a 
Experion Block. Or, 
deleting RCAS_IN or 
ROUT_IN connection 
from Fieldbus block 
and re-wiring it to 
block's CAS_IN pin.  
The control VCR formed 
when the RCAS_IN or 
ROUT_IN connection was 
made is not removed.  
To remove this VCR, you must delete 
the Fieldbus block and then recreate it.