18. Appendix I
18.2. Description
550 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Tab
Parameter Default Value Description
Time Sync Class
(LMLSTREC.TIMSCL
S)
10ms
Specifies one of the time
synchronization classes. The
DLE uses it to record the Link's
time synchronization class and
to determine the DLE's own
requirement for the minimum
time distribution period it needs
to maintain the specified level of
time synchronization. Its default
value is 10 ms. The eight
classes are None,
1microsecond, 10
microseconds, 100
microseconds, 1 millisecond, 10
milliseconds, 100 milliseconds,
and 1 second.
Point Detail Page sysDtlLink.dsp
By default, a Display template is
already entered into the Point
Detail Page field (for example,
sysDtlLink.dsp). This template
can be used for creating your
own display or it can be used as
is, provided that your function
block name matches the name
built into the detail display that is
supplied as a template.
Associated Display Blank
Enter the name of the Server
Associated Display to be
associated with this function
block.
Server
Parameters
Group Detail Page sysgrpLink.dsp
By default, a Display template is
already entered into the Group
Detail Page field (for example,
sysgrpLink.dsp). This template
can be used for creating your
own display or it can be used as
is, provided that your function
block name matches the name
built into the detail display that is
supplied as a template.