NO TE
Trap Port is set to null by default.
3. Select the SNMP Version. If an SNMPv3 user is congured, it is recommended
that SNMP Version be set to SNMPv3.
4. If SNMP Version is set to SNMPv3, select an SNMPv3 user name, and then
tap as shown in Figure 4-27.
Figure 4-27 Setting SNMP trap parameters
5. Tap Submit under SNMP Trap.
----End
Follow-up Procedure
After a USB ash drive has been inserted into the controller USB port and
successfully
identied, tap Export File under MIB File to export the MIB le to the
USB ash drive for the customer's use in accessing a third-party EMS. Figure 4-28
shows successful
le export.
NO TICE
Before using a USB ash drive, ensure that its data has been scanned by antivirus
software and is secure.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 152