Figure 4-38 Selecting commissioning items
NO TE
If the system is not congured with the electric heater and humidier components, the
electric heater and humidier commissioning items will not appear on the screen.
If the heating function and humidication function are disabled, you cannot select the
electric heater and humidier items.
All the items are selected by default if you rst enter the screen where you select
commissioning items. Except that the indoor fan item is mandatory, you can clear other
commissioning items that are not required.
Step 5 Tap Yes, a dialog box is displayed as follows. Choose whether to select Humidier
commissioning or not onsite.
Figure 4-39 Dialog box
Step 6 Tap Conrm. The fan commissioning screen is displayed, as shown in Figure 4-40.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 163