Figure 3-20 Removing a liquid level detector transport fastener
3. Connect the interconnection terminal of the low liquid level detector as
shown in Figure 3-21.
The interconnection terminal of the high liquid level detector has been connected
before delivery.
Figure 3-21 Connecting the interconnection terminal
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 3 Installation Guide
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 50