Learning Advanced Features
147
measured with static auto tuning may be less accurate. Inaccuracy of the measured parameters
may degrade the performance of sensorless operation. Therefore, run static type auto tuning by
selecting 2 (All) only when the motor cannot be rotated (when gearing and belts cannot be
separated easily, or when the motor cannot be separated mechanically from the load).
In PM synchronous motor sensorless control mode, check the motors rating plate and enter the
motor specifications, such as the base frequency, pole number, rated current and voltage, and
efficiency, before performing auto tuning and detecting other motor parameters by setting bA.20
(Auto Tuning) to 7 [All (PM)]. The detected parameter values may not be accurate if the motors base
specifications are not entered.
5.10 Sensorless Vector Control for Induction Motors
Sensorless vector control is an operation to carry out vector control without the rotation speed
feedback from the motor but with an estimation of the motor rotation speed calculated by the
inverter. Compared to V/F control, sensorless vector control can generate greater torque at a lower
level of current.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
dr
09
Control mode
Control Mode
4
IM Sensorless
-
-
14
Motor capacity
Motor Capacity
Depends on the
motor capacity
0-15
-
18
Base frequency
Base Freq
60
30-400
Hz
bA
11
Motor pole number
Pole Number
4
2-48
-
12
Rated slip speed
Rated Slip
Depends on the
motor capacity
0-3000
Hz
13
Rated motor current
Rated Curr
Depends on the
motor capacity
1-1000
A
14
Motor no-load current
Noload curr
Depends on the
motor capacity
0.5-1000
A
15
Rated motor voltage
Rated Volt
220/380/440/480
170-480
V
16
Motor efficiency
Efficiency
Depends on the
motor capacity
64-100
%
20
Auto tuning
Auto Tuning
1
All
-
-
Cn
09
Pre-Excite time
PreExTime
1.0
0.0-60.0
s
10
Pre-Excite amount
Flux Force
100.0
100.0-300.0
%
20
Sensorless second gain
display setting
SL2 G View Sel
1
Yes
0-1
-
21
Sensorless speed
controller proportional
gain1
ASR-SL P Gain1
Depends on the
motor capacity
0-5000
%
22
Sensorless speed
controller integral gain 1
ASR-SL I Gain1
Depends on the
motor capacity
10-9999
ms

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals