225
Learning Protection Features
Code
Description
In.65-71 Px Define
Press [Stop/Reset] key on the keypad or use the multi-function input terminal to
restart the inverter. Set the multi-function input terminal to 3 (RST) and turn on
the terminal to reset the trip status.
6.3.6 Inverter Diagnosis State
Check the diagnosis of components or devices for inverter to check if they need to be replaced.
Group Code Name LCD Display
Parameter
Setting
Setting Range Unit
PRT 89
C A P, FA N
replacement
warning
Inverter State
Bit
00-10
Bit
00
-
01
CAP Warning
10
FAN Warning
6.3.7 Operation Mode on Option Card Trip
Option card trips may occur when an option card is used with the inverter. Set the operation mode
for the inverter when a communication error occurs between the option card and the inverter body, or
when the option card is detached during operation.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
Pr
80
Operation mode on option
card trip
Opt Trip Mode
0
None
0-3
-
1
Free-Run
2
Dec
Operation Mode on Option Trip Setting Details
Code
Description
Pr.80 Opt Trip Mode
Setting
Function
0
None
No operation
1 Free-Run
The inverter output is blocked and fault trip
information is shown on the keypad.
2 Dec
The motor decelerates to the value set at Pr.07 (Trip
Dec Time).