95
Learning Basic Features
Note that actual Acc/Dec times become greater than user defined Acc/Dec times when S-curve
Acc/Dec patterns are in use.
4.12 Stopping the Acc/Dec Operation
Configure the multi-function input terminals to stop acceleration or deceleration and operate the
inverter at a fixed frequency.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
In
6571
Px terminal
configuration
Px Define(Px: P1
P7)
25
XCEL Stop
054
-
4.13 V/F(Voltage/Frequency) Control
Configure the inverters output voltages, gradient levels and output patterns to achieve a target
output frequency with V/F control. The amount of of torque boost used during low frequency
operations can also be adjusted.
4.13.1 Linear V/F Pattern Operation
A linear V/F pattern configures the inverter to increase or decrease the output voltage at a fixed
rate for different operation frequencies based on V/F characteristics. A linear V/F pattern is
partcularly useful when a constant torque load is applied.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
dr
09
Control mode
Control Mode
0
V/F
0–4
-
18
Base frequency
Base Freq
60.00
30.00400.00
Hz