74
Learning Basic Features
4.1.4 Setting a Frequency Reference with Input Voltage (Terminal I2)
Set and modify a frequency reference using input voltage at I2 (V2) terminal by setting SW2 to V2.
Set the Frq (Frequency reference source) code in the Operation group to 4 (V2) and apply 012V
input voltage to I2 (=V2, Analog current/voltage input terminal). Codes In.3547 will not be
displayed when I2 is set to receive current input (Frq code parameter is set to 5).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation Frq
Frequency
reference source
Freq Ref Src 4 V2 012 -
In
35
V2 input display
V2 Monitor
0.00
0.0012.00
V
37
V2 input filter time
constant
V2 Filter 10 010000 ms
38
Minimum V2 input
voltage
V2 Volt x1 0.00 0.0010.00 V
39
Output% at
minimum V2
voltage
V2 Perc y1 0.00 0.00100.00 %
40
Maximum V2 input
voltage
V2 Volt x2 10.00 0.0010.00 V
41
Output% at
maximum V2
voltage
V2 Perc y2 100.00 0.00100.00 %
46
Invert V2 rotational
direction
V2 Inverting 0 No
01
-
47 V2 quantizing level V2 Quantizing 0.04
0.00*, 0.04
10.00
%
* Quantizing is disabled if 0’ is selected.
4.1.5 Setting a Frequency with TI Pulse Input
Set a frequency reference by setting the Frq (Frequency reference source) code in Operation
group to 12 (Pulse). In case of Standard I/O, set the In.69 P5 Define to 54(TI) and providing 0
32.00kHz pulse frequency to P5.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation Frq
Frequency
reference source
Freq Ref Src 12 Pulse 012 -
In
69
P5 terminal
function setting
P5 Define 54 TI 0-54 -
01
Frequency at
maximum analog
input
Freq at 100% 60.00
0.00
Maximum
frequency
Hz