85
Learning Basic Features
Forward/Reverse Run Prevention Setting Details
Code
Description
Ad.09 Run Prevent
Choose a direction to prevent.
Setting
Description
0
None
Do not set run prevention.
1
Forward Prev
Set forward run prevention.
2
Reverse Prev
Set reverse run prevention.
4.8 Power-on Run
A power-on command can be setup to start an inverter operation after powering up, based on
terminal block operation commands (if they have been configured). To enable power-on run set
the drv (command source) code to 1(Fx/Rx-1) or 2 (Fx/Rx-2) in the Operation group.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation drv Command source Cmd Source* 1, 2
Fx/Rx-1 or
Fx/Rx-2
0–5 -
Ad
10
Power-on run
Power-on Run
1
Yes
0–1
-
* Displayed under DRV-06 on the LCD keypad.
Note
A fault trip may be triggered if the inverter starts operation while a motors load (fan-type load) is
in free-run state. To prevent this from happening, set bit4 to 1 in Cn. 71 (speed search options) of
the Control group. The inverter will perform a speed search at the beginning of the operation.
If the speed search is not enabled, the inverter will begin its operation in a normal V/F pattern and
accelerate the motor. If the inverter has been turned on without power-on run enabled, the
terminal block command must first be turned off, and then turned on again to begin the inverters
operation.