Learning Advanced Features
5.22 Read, Write, and Save Parameters
Use read, write and save function parameters on the inverter to copy parameters from the inverter
to the keypad or from the keypad to the inverter.
CNF*
*Available on LCD keypad only.
Read, Write, and Save Parameter Setting Details
CNF-46 Parameter Read
Copies saved parameters from the inverter to the keypad. Saved parameters
on the keypad will be deleted and replaced with copied parameters.
CNF-47 Parameter Write
Copies saved parameters from the keypad to the inverter. Saved parameters
on the inverter will be deleted and replaced with copied parameters. If an
error occurs during parameter writing, previous saved data will be used. If
there is no saved data on the Keypad,
‘EEP Rom Empty’ message will be
CNF-48 Parameter Save
As parameters set during communication transmission are saved to RAM,
the setting values will be lost if the power goes off and on. When setting
parameters during communication transmission, select 1 (Yes) from CNF-48
code to save the set parameter.
5.23 Parameter Initialization
User changes to parameters can be initialized (reset) to factory default settings on all or selected
groups. However, during a fault trip situation or operation, parameters cannot be initialized.
dr* 93 Parameter initialization - 0 No
0–16
CNF** 40 Parameter initialization Parameter Init 0 No 0–16
* For keypad
** For LCD keypad