Learning Advanced Features
CNF-12 KPD title Ver Checks title version on the LCD keypad.
CNF-30–32 Option-x type
Checks type of powerboard installed in 1–3 power slot.
CNF-44 Erase all trip Deletes stored trip history.
CNF-60 Add Title Up
When inverter SW version is updated and more code is added, CNF-60
settings will add, display, and operate the added codes. Set CNF-60 to
1(Yes) and disconnect the LCD keypad from the inverter. Reconnecting the
LCD keypad to the inverter updates titles.
CNF-62 WH Count Reset Initialize accumulated electric energy consumption count.
5.30 Timer Settings
Set a multi-function input terminal to a timer and On/Off control the multi-function output and
relay according to the timer settings.
In 65–71
Px terminal
configuration
38 Timer In - -
OU
28 Timer Out - -
Timer Setting Details
In.65–71 Px Define
Choose one of the multi-function input terminals and change it to a timer
terminal by setting it to 38 (Timer In).
OU.31 Relay1,
OU.33 Q1 Define
Set multi-function output terminal or relay to be used as a timer to 28 (Timer
out).
OU.55 TimerOn Delay,
OU.56 TimerOff Delay
Input a signal (On) to the timer terminal to operate a timer output (Timer out)
after the time set at OU.55 has passed. When the multi-function input terminal
is off, multi-function output or relay turns off after the time set at OU.56.