Learning Advanced Features
1 Set OU.07 (AO2 Mode) to constant, and set OU.11 (AO2 Const %) to 0.0 %.
2 Set OU.09 (AO2 Bias) to 20.0% and then check current output. 4mA output should be displayed.
3 If the value is less than 4mA, gradually increase OU.09 (AO2 Bias) until 4mA is measured. If the
value is more than 4mA, gradually decrease OU.09 (AO2 Bias) until 4mA is measured.
4 Set OU.11 AO2 Const % to 100.0%
Set OU.08 (AO2 Gain) to 80.0% and measure current output at 20mA. If the value is less than
20mA, gradually increase OU.08 (AO2 Gain) until 20mA is measured. If the value is more than
20mA, gradually decrease OU.08 (AO2 Gain) until 20mA is measured.
The functions for each code are identical to the descriptions for the 0–10V voltage outputs with an
output range 4–20mA.
5.35 Digital Output
5.35.1 Multi-function Output Terminal and Relay Settings
OU
31
Multi-function relay1
setting
Relay 1 29 Trip - -
33
Multi-function output1
setting
Q1 Define 14 Run - -
41
Multi-function output
monitor
DO Status - 00– 11 bit
0.00–Maximum
frequency
Hz
58
FDT Band 10.00
In
65–71
Px terminal configuration Px Define 16 Exchange - -
*Displayed as on the keypad.
Multi-function Output Terminal and Relay Setting Details
Set relay (Relay 1) output options.
OU.33 Q1 Define
Select output options for multi-function output terminal (Q1). Q1 is open collector
TR output.
Set output terminal and relay functions according to OU.57 FDT (Frequency),