Learning Advanced Features
197
1 Set OU.07 (AO2 Mode) to constant, and set OU.11 (AO2 Const %) to 0.0 %.
2 Set OU.09 (AO2 Bias) to 20.0% and then check current output. 4mA output should be displayed.
3 If the value is less than 4mA, gradually increase OU.09 (AO2 Bias) until 4mA is measured. If the
value is more than 4mA, gradually decrease OU.09 (AO2 Bias) until 4mA is measured.
4 Set OU.11 AO2 Const % to 100.0%
Set OU.08 (AO2 Gain) to 80.0% and measure current output at 20mA. If the value is less than
20mA, gradually increase OU.08 (AO2 Gain) until 20mA is measured. If the value is more than
20mA, gradually decrease OU.08 (AO2 Gain) until 20mA is measured.
The functions for each code are identical to the descriptions for the 010V voltage outputs with an
output range 420mA.
5.35 Digital Output
5.35.1 Multi-function Output Terminal and Relay Settings
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
OU
30
Fault output item
Trip Out Mode
010*
-
bit
31
Multi-function relay1
setting
Relay 1 29 Trip - -
33
Multi-function output1
setting
Q1 Define 14 Run - -
41
Multi-function output
monitor
DO Status - 00 11 bit
57
Detection frequency
FDT Frequency
30.00
0.00Maximum
frequency
Hz
58
Detection frequency
band
FDT Band 10.00
In
6571
Px terminal configuration Px Define 16 Exchange - -
*Displayed as on the keypad.
Multi-function Output Terminal and Relay Setting Details
Code
Description
OU.31 Relay1
Set relay (Relay 1) output options.
OU.33 Q1 Define
Select output options for multi-function output terminal (Q1). Q1 is open collector
TR output.
OU.41 DO Status
Set output terminal and relay functions according to OU.57 FDT (Frequency),