192
Learning Advanced Features
Code
Description
Ad.76 CompFreq Limit
Set alternative frequency width that can replace actual operation frequency
during regeneration prevention.
Ad.77 RegenAvd Pgain,
Ad.78 RegenAvd Igain
To prevent regeneration zone, set P gain/I gain in the DC link voltage supress
PI controller.
Note
Press regeneration prevention does not operate during accelerations or decelerations, but it only
operates during constant speed motor operation. When regeneration prevention is activated, output
frequency may change within the range set at Ad.76 (CompFreq Limit).
5.34 Analog Output
An analog output terminal provides output of 010V voltage, 420mA current, or 032kHz pulse.
5.34.1 Voltage and Current Analog Output
An output size can be adjusted by selecting an output option at AO(Analog Output) terminal. Set
the analog voltage/current output terminal setting switch (SW3) to change the output type
(voltage/current).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
OU
01
Analog output1
AO1 Mode
0
Frequency
015
-
02
Analog output1 gain
AO1 Gain
100.0
-1000.01000.0
%
03
Analog output1 bias
AO1 Bias
0.0
-100.0100.0
%