99
Learning Basic Features
Manual Torque Boost Setting Details
Code
Description
dr.16 Fwd Boost
Set torque boost for forward operation.
dr.17 Rev Boost
Set torque boost for reverse operation.
Excessive torque boost will result in over-excitation and motor overheating .
4.14.2 Auto Torque Boost-1
Auto torque boost enables the inverter to automatically calculate the amount of output voltage
required for torque boost based on the entered motor parameters. Because auto torque boost
requires motor-related parameters such as stator resistance, inductance, and no-load current, auto
tuning (bA.20) has to be performed before auto torque boost can be configured [Refer to 5.9
Auto
Tuning on page 144]. Similarly to manual torque boost, configure auto torque boost while running
a load that requires high starting torque, such as lift-type loads.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Dr
15
torque boost mode
Torque Boost
1
Auto1
0–2
-
bA
20
auto tuning
Auto Tuning
3
Rs+Lsigma
0–6
-

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals