Learning Protection Features
6.2.4 Speed Command Loss
When setting operation speed using an analog input at the terminal block, communication
options, or the keypad, speed command loss setting can be used to select the inverter operation
for situations when the speed command is lost due to the disconnection of signal cables.
Speed command loss
operation mode
Time to determine
speed command loss
at speed command
frequency–
decision level
Command
Speed Command Loss Setting Details
In situations when speed commands are lost, the inverter can be configured to
operate in a specific mode:
The speed command immediately becomes the
operation frequency without any protection
The inverter blocks output. The motor performs in
free-run condition.
The motor decelerates and then stops at the time
set at Pr.07 (Trip Dec Time).
The inverter calculates the average input value for
10 seconds before the loss of the speed command
and uses it as the speed reference.
The inverter calculates the average output value for
10 seconds before the loss of the speed command
and uses it as the speed reference.
The inverter operates at the frequency set at Pr. 14
(Lost Preset F).
Pr.13 Lst Cmd Time
Configure the voltage and decision time for speed command loss when using
analog input.
Based on the values set at In.08 and In.12,