90
Learning Basic Features
Acc/Dec Time Based on Operation Frequency Setting Details
Code
Description
bA.08
Ramp T Mode
Set the parameter value to 1 (Delta Freq) to set Acc/Dec times based on
Maximum frequency.
Configuration
Description
0
Max Freq
Set the Acc/Dec time based on Maximum
frequency.
1
Delta Freq
Set the Acc/Dec time based on Operation
frequency.
If Acc/Dec times are set to 5 seconds, and multiple frequency references are used
in the operation in 2 steps, at 10Hz and 30 Hz, each acceleration stage will take 5
seconds (refer to the graph below).
4.10.3 Multi-step Acc/Dec Time Configuration
Acc/Dec times can be configured via a multi-function terminal by setting the ACC (acceleration
time) and dEC (deceleration time) codes in the Operation group.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation
ACC
Acceleration time
Acc Time
20.0
0.0600.0
sec
dEC
Deceleration time
Dec Time
30.0
0.0600.0
sec
bA
7082
Multi-step
acceleration time17
Acc Time 17
x.xx 0.0600.0 sec
7183
Multi-step
deceleration time17
Dec Time 17 x.xx 0.0600.0 sec
In
6571
Px terminal
configuration
Px Define
(Px: P1–P7)
11
XCEL-L
054 -
12
XCEL-M
49
XCEL-H
89
Multi-step command
delay time
In Check Time 1 15000 ms