221
Learning Protection Features
6.3.1 Fan Fault Detection
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
Pr
79
Cooling fan fault selection
FAN Trip Mode
0
Trip
OU
31
Multi-function relay 1
Relay 1
8
FAN Warning
-
OU
33
Multi-function output 1
Q1 Define
Fan Fault Detection Setting Details
Code
Description
Pr.79 FAN Trip Mode
Set the cooling fan fault mode.
Setting
Function
0
Trip
The inverter output is blocked and the fan trip is
displayed when a cooling fan error is detected.
1
Warning
When OU.33 (Q1 Define) and OU.31 (Relay1) are set
to 8 (FAN Warning), the fan error signal is output
and the operation continues.
OU.33 Q1 Define,
OU.31 Relay1
When the code value is set to 8 (FAN Warning), the fan error signal is output and
operation continues. However, when the inverter inside temperature rises
above a certain level, output is blocked due to activation of overheat protection.
6.3.2 Lifetime diagnosis of components
Registering a capacitance reference for inspection
Note
To perform a capacitor diagnosis, a capacitance reference must be measured and registered by setting
Pr-61 (CAP Diag) to 1 (Ref Diag) when the inverter is used for the first time. The measured reference
value is saved at Pr-63 and is used asthe reference for the capacitor life diagnosis.
Refer to the following instructions to measure a reference capacitance.
1 Set an appropriate capacitor diagnosis current based on the inverters rated output at Pr-60
(CAP DiagCurr).
The capacitor diagnosis current is a direct current that is applied to the capacitor for
inspection, and is defined asin a percentage of the rated inverter output. Because the value
is defined based on the inverter output, set an appropriate value if the motor has smaller
rated current.
2 At Pr-62 (CAP Exchange Level), set the capacitor replacement warning level to a value
between 50.0% and 95.0%