232
RS-485 Communication Features
Code
Description
CM.05 Resp Delay
Set the response time for the slave (inverter) to react to the request from the
master. Response time is used in a system where the slave device response is
too fast for the master device to process. Set this code to an appropriate value
for smooth master-slave communication.
7.2.3 Setting Operation Command and Frequency
To select the built-in RS485 communication as the source of command, set the Frq code to 6
(Int485) on the keypad (basic keypad with 7-segment display). On an LCD keypad, set the DRV
code to 3 (Int485). Then, set common area parameters for the operation command and
frequency via communication.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
Pr
12
Speed command loss
operation mode
Lost Cmd Mode
1
Free-Run
0-5
-
13
Time to determine speed
command loss
Lost Cmd Time
1.0
0.1-120
s
14
Operation frequency at
speed command loss
Lost Preset F
0.00
Start
frequency
Maximum
frequency
Hz
OU
31
Multi-function relay 1
Relay 1
13
Lost
Command
0-35
-
33
Multi-function output 1
Q1 Define