RS-485 Communication Features
Built-in communication
inverter ID
Built-in communication
protocol
Built-in communication
speed
Built-in communication
frame setting
Transmission delay after
reception
Communication Parameters Setting Details
Set the inverter station ID between 1 and 250.
Select one of the two built-in protocols: Modbus-RTU or LS INV 485.
Modbus-RTU compatible protocol
Dedicated protocol for the LS inverter
Set a communication setting speed up to 115,200 bps.
Set a communication configuration. Set the data length, parity check method,
and the number of stop bits.
8-bit data / no parity check / 1 stop bit
8-bit data / no parity check / 2 stop bits
8-bit data / even parity / 1 stop bit
8-bit data / odd parity / 1 stop bit