102
Learning Basic Features
4.17 Stop Mode Setting
Select a stop mode to stop the inverter operation.
4.17.1 Deceleration Stop
Deceleration stop is a general stop mode. If there are no extra settings applied, the motor
decelerates down to 0Hz and stops, as shown in the figure below.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Ad 08 Stop mode Stop Mode 0 Dec
04
-
4.17.2 Stop After DC Braking
When the operation frequency reaches the set value during deceleration (DC braking frequency),
the inverter stops the motor by supplying DC power to the motor. With a stop command input,
the inverter begins decelerating the motor. When the frequency reaches the DC braking
frequency set at Ad.17, the inverter supplies DC voltage to the motor and stops it.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Ad
08 Stop mode Stop Mode 0 Dec
04
-
14
Output block time
before braking
DC-Block Time 0.10 0.0060.00 sec
15
DC braking time
DC-Brake Time
1.00
060
sec
16
DC braking amount
DC-Brake Level
50
0200
%
17
DC braking frequency
DC-Brake Freq
5.00
0.0060.00
Hz