29
Jump frequency
upper limit1
Jump Hi 1 15.00
Jump frequency lower limit
1–Maximum frequency
Hz
30
Jump frequency
lower limit 2
Jump Lo 2 20.00
0.00–Jump frequency upper
limit 2
Hz
31
Jump frequency
upper limit 2
Jump Hi 2 25.00
Jump frequency lower limit
2–Maximum frequency
Hz
32
Jump frequency
lower limit 3
Jump Lo 3 30.00
0.00–Jump frequency upper
limit 3
Hz
33
Jump frequency
upper limit 3
Jump Hi 3 35.00
Jump frequency lower limit
3–Maximum frequency
Hz
4.19 2
nd
Operation Mode Setting
Apply two types of operation modes and switch between them as required. For both the first and
second command source, set the frequency after shifting operation commands to the multi-
function input terminal. Mode swiching can be used to stop remote control during an operation
using the communication option and to switch operation mode to operate via the local panel, or
to operate the inverter from another remote control location.
Select one of the multi-function terminals from codes In. 65–71 and set the parameter value to 15
(2nd Source).
Opera
tion
Frq
Frequency reference
source
Freq Ref Src 2 V1 0–12 -