Learning Advanced Features
201
Code
Description
35
BR Control
Outputs a brake release signal.
Refer to 5.31 Brake Control on page 189.
40
KEB Operating
This outputs when the energy buffering operation is
started because of low voltage of the inverter's DC
power section due to a power failure on the input
power. ( This outputs in the energy buffering state
before the input power restoration regardless of KEB-
1 and KEB-2 mode settings.)
5.35.2 Fault Trip Output using Multi-Function Output Terminal and
Relay
The inverter can output fault trip state using multi-function output terminal (Q1) and relay (Relay
1).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
OU
30
Fault trip output mode
Trip Out Mode
010
-
bit
31
Multi-function relay1
Relay 1
29
Trip
-
-
33
Multi-function output1
Q1 Define
14
Run
-
-
53
Fault trip output on delay
TripOut OnDly
0.00
0.00100.00
sec
54
Fault trip output off delay
TripOut OffDly
0.00
0.00100.00
sec
Fault Trip Output by Multi-function Output Terminal and Relay - Setting Details
Code
Description
OU.30 Trip Out Mode
Fault trip relay operates based on the fault trip output settings.
Item
bit on
bit off
Keypad
LCD keypad
Select fault trip output terminal/relay and select 29(Trip Mode) at codes OU.
31, 33. When a fault trip occurs in the inverter, the relevant terminal and relay
will operate. Depending on the fault trip type, terminal and relay operation
can be configured as shown in the table below.
Setting
Function
bit3
bit2
bit1
Operates when low voltage fault trips occur
Operates when fault trips other than low voltage